DATA LOGGER MX-8
MX-8 Data Logger records pulse output signals from various accounting devices: meters, sensors (pressure, temperature), through a serial interface. It records the number of pulses seen during each logging interval and transmits all existing and collected data to a server through 2G, 3G, 4G or NB-IoT connection, on a specified frequency. This data logger is battery powered, suitable for even more applications.
Application possibilities
Data Logger MX-8 is dedicated for reading Wireless M-Bus meters, real time logging and analyzing of data. Using GPRS/GSM or Ethernet, logger sends data to remote users / server. MX-8 can also communicate with other controllers and sensors. Device has wide range of optional interfaces and protocols and can read any kind of meters, controllers and sensors equipped with standard protocols. Perfect for smart metering of commercial, residential or industrial buildings.
Water metering
Environmental monitoring
Electricity metering
Renewable energy monitoring
Gas metering
Industrial metering and control
Heat substation metering
Wireless M-Bus metering
Smart house
Commercial metering
Device adjustment to client’s needs
If client needs custom made application or special functions, our R&D department ready to help. We can adjust our devices, include special protocols or interfaces to meet client application’s needs. Also we are ready to adjust our device for working with various meters, flow meters (even exotic ones). If you are not sure if our device can satisfy your needs, feel free to contact us anytime.
MX-9 can read: Kamstrup, Sensus, Danfoss, L+G, Itron, Diehl, Apataor and other manufacturer’s meters. Also MX-9 can read and controll other controllers, like Danfoss ECL 300.
Application examples
Below indicated few samples how MX-8 collects the data from Wireless M-Bus meters / sensors and controllers and sends the data to local or remote users using Modbus protocol via GPRS / GSM or Ethernet. There is so many ways to use our MX-8. Starting from smart metering (from WIreless M-Bus meters), heating substation metering, data acquisition from temperature, pressure sensors, data acquisition from weather stations and sensors, chemical monitoring and telemetry, to smart house telemetry, and scientific device monitoring and telemetry.
– Calculate the pulses of the accounting devices;
– Read values of meters or sensors (pressure, temperature) through a serial interface;
– Store meters data in memory at selected intervals;
– Track data values and transmit deviation information in the event of deviations from specified thresholds;
– Transmits all existing and collected data to a server on a 2G, 3G, 4G or NB-IoT connection at a specified frequency;
– Perform all these functions without external power.
Description | Data Logger MX-8 technical specifications |
---|---|
Pulse inputs | |
Amount | 1 or 2 |
Input type | “dry contact” |
Minimum pulse period | 50 ms |
Minimum pulse duration | 20 ms |
Detected disconnected input | Yes |
Serial communication interfaces | |
Amount | 1 |
Interface type: | M-Bus (up to 10 M-Bus devices) RS485 I2C |
Quantity of metering devices connected to the M-bus interface |
2 |
Data speed over M-bus or RS485 interfaces |
300 – 9600 M-Bus 300 – 115200 Modbus |
Periodicity of data reading via M-bus interface |
4 band 850/900/1800/1900 MHz |
Frequency of reading data via RS485 interface |
15min – 24 hours |
Remote data transmission | |
Available type of transmission type | 2G, 3G, 4G or NB-IoT |
Frequency of data transmission | At least once daily or in the event of a deviation |
Data transmitted | – Cumulative periodic data for at least the last 3 months. If accumulation is performed every 1 hour. Only data that was not transmitted during the previous connection is transmitted – Alerts data. Transmissions shall be promptly recorded when deviation from the boundaries of the task or external influences are recorded – Identification: Number, version, user-defined identification, time, battery parameters |
Data Communication Protocol | HTTP, FTP |
Communication antenna | Internal or external |
SIM Card | SIM (25×15). Insert / replace socket without tools. Changing is done by removing the storage cap |
Configuration | |
Type | USB 2.0 |
Purpose | For local data scanning, configuration and diagnostics |
Connecting | Through an external connection without opening the inverter housing |
Power supply | |
Type | Internal 14Ah battery, plugs in and replaces without the need for tools |
Duration of operation (converter operation) |
At least 4 years under conditions: Data transfer to server no more than once a day, M-bus scan no more than once a day |
Battery Status Monitoring | Yes. Energy, voltage, temperature are measured |
Physical characteristics | |
Fixing type | mount on the wall |
Protection type | IP68 or IP65 |
Dimensions | IP68 class 146 mm x 114 mm x 62 mm IP68 class 114 mm x 114 mm x 62 mm IP65 class 120 mm x 120 mm x 60 mm |
Connection type | IP68 class: per IP68 class connectors |
Working conditions | |
Operating temperature | -25 oC… +60oC |
Storage temperature | – 40 oC …+60oC |
Real time clock | |
Error without synchronization | ±5s per day |
Synchronization | From GSM network and / or server during data transmission |
Other features | |
Local Activation | External magnetic field or USB |